| Input Type | mV,V | mA |
| Input Resistance | 330 Ohm | 100 Ohm |
| Galvanic Isolation | 4,0 kV | |
| Accuracy | 0,1% F.S.R. | |
| Linearity Error | <0.02% | |
| Max. Load Impedance | >1kOhm (V) | 400 Ohm (mA) |
| Rise Time (10-90%) | 10 ms | |
| Transmission Frequency | <30Hz | |
| Operating Voltage Range | DC 16, 8-264 V | AC 19, 2-264 V |
| Rated Current | 12 mA | |
| Temperature Coefficient | 150 ppm/ºK F.S.R. | |
| Operating Temperature | -25ºC to +60ºC | |
| Storage Temperature | -40ºC to +85ºC | |
| E.M.C. | ||
| Generic Immunity | EN 61000-6-2 | |
| Generic Temperature | EN 61000-6-3 |
DIN KOS517 Signal Converter
Configurable signal converter
- 16 input ranges in mV, mA, V
- Configurable voltage output 0-10V or current output 0/4-20mA
- 3 ways 4 kV Isolation
- Power supply: 24-240 VAC/DC
Content missing
Related Products
-
The KOS1200 is a (4 - 20mA) Signal isolator powered at input and output loops. The small size enables many more units to now be installed in the same physical space. Th...
KOS1200 Double Isolator
The KOS1200 is a (4 - 20mA) Signal isolator powered at input and output loops. The small size enables many more…
-
Installation Kit on DIN RAIL for in-head converters. The kit ACK103 (KOS Converters) Includes: A. 1 M4 screws to secure the support to the converter. B. 1 Support m...
Mounting Device on DIN Rail for KOS Series ACK103
Installation Kit on DIN RAIL for in-head converters. The kit ACK103 (KOS Converters) Includes: A. 1 M4 screws to secure…