| Input Signal | 0-1A,±1A | 0-5A,±5A |
| Zero/Span | Pre-calibrated | |
| Input Resistance | 0,1 Ohm | 0,05 Ohm |
| Frequency Range | 15-400Hz | |
| Isolation | 1,5kV (3 way) | |
| Accuracy | 0,5% F.S.R. | |
| Linearity Error | 0,10% | |
| Max. Load Impedance | >1kOhm (V) | 400 Ohm (mA) |
| Operating Voltage range | DC 16,8-30V | |
| Rated Current | 13 mA | |
| Temperature Coefficient | 150 ppm/ºK F.S.R. | |
| Operating Temperature | -25ºC to +60ºC | |
| Storage Temperature | -40ºC to +85ºC | |
| E.M.C. | ||
| Generic Immunity | EN 61000-6-2 | |
| Generic Temperature | EN 61000-6-3 |
DIN KOS540 Signal Converter
AC/DC Current Converter
- Input 0-1 A
- Configurable voltage output 0-10V or Current output 0/4-20mA
- 3 ways 1,5 Kv Isolation
- Power Supply 24Vdc